Please use this identifier to cite or link to this item: http://bura.brunel.ac.uk/handle/2438/4872
Title: The most economical power factor correction according to tariff structures in Egypt
Authors: Zobaa, AF
Aziz, MMA
Keywords: Harmonics;Power factor;Reactive power optimization
Issue Date: 2005
Publisher: IEEE
Citation: IEEE Transactions on Power Delivery, 20(2): 912-918, Apr 2005
Abstract: A method of applying power-factor (PF) correction capacitors is discussed based on net savings maximization according to Egyptian's Tariff. Test results from examples taken from existing publications are presented. The purpose of this application technique is to utilize existing electrical distribution equipment in the installation of very large values of PF correction capacitors. It is concluded that LC compensators can be installed, thus providing maximum benefits from penalty elimination, system losses reduction, release of system transformer capacity, and minimum switching transients. Paybacks of less than one year can be expected.
Description: This material is posted here with permission of the IEEE. Such permission of the IEEE does not in any way imply IEEE endorsement of any of Brunel University's products or services. Internal or personal use of this material is permitted. However, permission to reprint/republish this material for advertising or promotional purposes or for creating new collective works for resale or redistribution must be obtained from the IEEE by writing to pubs-permissions@ieee.org. Copyright @ 2005 IEEE
URI: http://bura.brunel.ac.uk/handle/2438/4872
DOI: http://dx.doi.org/10.1109/TPWRD.2004.839178 
ISSN: 0885-8977
Appears in Collections:Electronic and Computer Engineering
Dept of Electronic and Electrical Engineering Research Papers

Files in This Item:
File Description SizeFormat 
Fulltext.pdf289.05 kBAdobe PDFView/Open