Please use this identifier to cite or link to this item: http://bura.brunel.ac.uk/handle/2438/21673
Full metadata record
DC FieldValueLanguage
dc.contributor.authorAl-Zaidi, AH-
dc.contributor.authorMahmoud, MM-
dc.contributor.authorKarayiannis, TG-
dc.coverage.spatialVirtual-
dc.date.accessioned2020-10-22T08:41:41Z-
dc.date.available2020-10-22T08:41:41Z-
dc.date.issued2020-10-14-
dc.identifierPaper No. ICMFHT 124-
dc.identifier.citationAl-Zaidi, A.H., Mahmoud, M.M. and Karayiannins, T.G. (2020) 'Flow Boiling of HFE-7100 in Multi-Microchannels: Effect of Surface Material', Proceedings of the 5th World Congress on Momentum, Heat and Mass Transfer (MHMT'20), Virtual, 14-16 October, Paper No. ICMFHT 124, pp. 1-5. doi: 10.11159/icmfht20.124.en_US
dc.identifier.isbn978-1-927877-75-3-
dc.identifier.urihttps://bura.brunel.ac.uk/handle/2438/21673-
dc.description.abstractThe effect of surface material on the flow boiling characteristics in a multi-microchannel evaporator is described in this paper. HFE-7100, a dielectric and eco-friendly working fluid, was tested at atmospheric pressure, inlet sub-cooling of 5 K, base heat flux up to 433.5 kW/m2 and mass flux range 50–250 kg/m2s. Two heat sinks made of copper and aluminium were fabricated having the same channel dimensions giving a hydraulic diameter of 0.46 mm with a base area of 500 mm2. The average roughness was measured and the values were 0.286 μm and 0.192 μm for the copper and aluminium, respectively. The effect of surface material was not significant at low heat flux. However, it became significant at moderate and high wall heat fluxes. The flow patterns for the two microchannels were similar and included bubble, slug, churn and annular flow. The experimental results showed that the aluminium surface achieved on the average difference of 12% higher heat transfer coefficients than those found in the copper microchannel. It also gave higher flow boiling pressure drop; the average difference was up-to approximately 30%. The different surface microstructures in the two examined heat sinks could explain the different heat transfer and pressure drop behaviour.en_US
dc.format.extent1 - 5-
dc.format.mediumElectronic-
dc.language.isoenen_US
dc.publisherInternational ASET Inc. (MHMT Congress)en_US
dc.sourceProceedings of the 5th World Congress on Momentum, Heat and Mass Transfer (MHMT'20) Lisbon, Portugal Virtual Congress – October 2020-
dc.sourceProceedings of the 5th World Congress on Momentum, Heat and Mass Transfer (MHMT'20) Lisbon, Portugal Virtual Congress – October 2020-
dc.subjectflow boiling pressure dropen_US
dc.subjectheat transfer coefficienten_US
dc.subjectmicrochannelsen_US
dc.subjectmaterial effecten_US
dc.subjectelectronics coolingen_US
dc.titleFlow Boiling of HFE-7100 in Multi-Microchannels: Effect of Surface Materialen_US
dc.typeConference Paperen_US
dc.relation.isPartOfProceedings of the 5th World Congress on Momentum, Heat and Mass Transfer (MHMT'20) Lisbon, Portugal Virtual Congress – October 2020-
pubs.finish-date2020-10-16-
pubs.finish-date2020-10-16-
pubs.publication-statusPublished-
pubs.start-date2020-10-14-
pubs.start-date2020-10-14-
dc.identifier.eissn2371-5316-
Appears in Collections:Dept of Mechanical and Aerospace Engineering Research Papers