Please use this identifier to cite or link to this item: http://bura.brunel.ac.uk/handle/2438/29938
Title: A two-stage underfrequency load shedding strategy for microgrid groups considering risk avoidance
Authors: Wang, C
Wang, Z
Chu, S
Ma, H
Yang, N
Zhao, Z
Lai, CS
Lai, LL
Keywords: microgrid groups;conditional value at risk;underfrequency load shedding;load characteristics;power deficit
Issue Date: 9-May-2024
Publisher: Elsevier
Citation: Wang, C. et al. (2024) 'A two-stage underfrequency load shedding strategy for microgrid groups considering risk avoidance', Applied Energy, 367, 123343, pp. 1 - 19. doi: 10.1016/j.apenergy.2024.123343.
Abstract: Underfrequency load shedding is the third level protection measure to ensure the safe and stable operation of power systems, which can effectively prevent the rapid decrease in system frequency caused by power system failure. To compensate for the power deficit resulting from faults during the island operation of a microgrid, a two-stage underfrequency load shedding strategy for microgrid groups considering risk avoidance is proposed in this paper. The proposed strategy divides underfrequency load shedding into a fast load shedding stage and a risk avoidance load shedding strategy. The first stage is fast underfrequency load shedding considering the load frequency characteristics and voltage characteristics; the fast underfrequency load shedding in the first stage reduces the fast frequency decrease before the second stage load shedding operation. The second stage of load shedding is risk avoidance under frequent load shedding. The load shedding in this stage accounts for the risk loss caused by the nondeterminacy of the demand side load to the system load shedding while accounting for the load frequency and voltage characteristics. First, the conditional value at risk (CVaR) theory is introduced in this paper to analyze and determine the risk loss caused by load nondeterminacy on load shedding, and the severity of load shedding (SoLS) is adopted as the CVaR value of load shedding. Second, the underfrequency load shedding optimization model is constructed by taking the risk value of the load shedding conditions of the microgrid as the optimization index of load shedding. Finally, the performance of the proposed strategy is verified based on the improved IEEE-37 node system microgrid group model. The results show that the proposed two-stage load shedding strategy can effectively prevent a rapid decrease in system frequency and effectively reduce the risk loss caused by load nondeterminacy during load shedding.
Description: Data availability: The data that has been used is confidential.
URI: https://bura.brunel.ac.uk/handle/2438/29938
DOI: https://doi.org/10.1016/j.apenergy.2024.123343
ISSN: 0306-2619
Other Identifiers: ORCiD: Chun Sing Lai https://orcid.org/0000-0002-4169-4438
123343
Appears in Collections:Dept of Electronic and Electrical Engineering Research Papers

Files in This Item:
File Description SizeFormat 
FullText.pdfEmbargoed until 9 May 20251.89 MBAdobe PDFView/Open


This item is licensed under a Creative Commons License Creative Commons