Please use this identifier to cite or link to this item: http://bura.brunel.ac.uk/handle/2438/28953
Title: A multi-layer approach to DN 50 electric valve fault diagnosis using shallow-deep intelligent models
Authors: Liu, Y-K
Zhou, W
Ayodeji, A
Zhou, X-Q
Peng, M-J
Chao, N
Keywords: electric valve;vibration and acoustic signal;support vector machine;particle swarm optimization;deep belief network
Issue Date: 8-Aug-2020
Publisher: Elsevier on behalf of the Korean Nuclear Society
Citation: Liu, Y.-K. et al. (2021) 'A multi-layer approach to DN 50 electric valve fault diagnosis using shallow-deep intelligent models', Nuclear Engineering and Technology, 53 (1), pp. 148 - 163. doi: 10.1016/j.net.2020.07.001.
Abstract: Timely fault identification is important for safe and reliable operation of the electric valve system. Many research works have utilized different data-driven approach for fault diagnosis in complex systems. However, they do not consider specific characteristics of critical control components such as electric valves. This work presents an integrated shallow-deep fault diagnostic model, developed based on signals extracted from DN50 electric valve. First, the local optimal issue of particle swarm optimization algorithm is solved by optimizing the weight search capability, the particle speed, and position update strategy. Then, to develop a shallow diagnostic model, the modified particle swarm algorithm is combined with support vector machine to form a hybrid improved particle swarm-support vector machine (IPs-SVM). To decouple the influence of the background noise, the wavelet packet transform method is used to reconstruct the vibration signal. Thereafter, the IPs-SVM is used to classify phase imbalance and damaged valve faults, and the performance was evaluated against other models developed using the conventional SVM and particle swarm optimized SVM. Secondly, three different deep belief network (DBN) models are developed, using different acoustic signal structures: raw signal, wavelet transformed signal and time-series (sequential) signal. The models are developed to estimate internal leakage sizes in the electric valve. The predictive performance of the DBN and the evaluation results of the proposed IPs-SVM are also presented in this paper.
Description: Research data for this article: Data not available / Data will be made available on request.
Supplementary data are available online at: https://www.sciencedirect.com/science/article/pii/S1738573320300279#appsec1 .
URI: https://bura.brunel.ac.uk/handle/2438/28953
DOI: https://doi.org/10.1016/j.net.2020.07.001
ISSN: 1738-5733
Other Identifiers: ORCiD: Abiodun Ayodeji https://orcid.org/0000-0003-3257-7616
Appears in Collections:Brunel Innovation Centre

Files in This Item:
File Description SizeFormat 
FullText.pdfCopyright © 2020 Korean Nuclear Society, Published by Elsevier Korea LLC. This is an open access article under the CC BY-NC-ND license (https://creativecommons.org/licenses/by-nc-nd/4.0/).5.21 MBAdobe PDFView/Open


This item is licensed under a Creative Commons License Creative Commons